EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
105
Don't forget to turn off this mode after the commissioning.
31.2. SENSITIVE FAULT DETECTION MODE (H5/A2)
To increase the possibilities to detect faults during the commissioning, it is possible to use the "Sensitive fault detection mode". The
time delay for each fault will then be reduced, i.e. you might find some faults now instead of later. The "Sensitive fault detection
mode" turned on is indicated by the LED Routing equipment "Fault tx activated" and the "Fault" output for routing equipment is
"activated" and in the display's symbol area.
a) Log on to the c.i.e.
b) Navigate to menu A2.
c) If sensitive fault detection mode is not active: Press
to activate.
d) If sensitive fault detection mode is activated: Press
to deactivate.
e) To exit the menu press ESC
.