EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
107
If you get “No reply from control unit.....” the control unit don't exist or don't answer.
31.4. DISPLAY CURRENT CONSUMPTION IN UNIT (H5/A4)
POWER SUPPLY (CONTROL UNIT)
Voltage
: The 24V measured by the CPU on the main board. Corresponds to the output voltage at the power supply outputs on
connector J3.
Earth voltage
: Measured from 0V (connector J4:2) to earth.
Current from power supply
: The total current consumption (including the charging current at 24V) for the selected control unit
(c.i.e.) when it is connected to the mains (230 V AC), i.e. this function is not working by battery backup.
BATTERY
Voltage
: The battery voltage at connector J4:4-5.
Charging current
: The battery charging current for the selected control unit (c.i.e.).
Temperature
: The temperature detected by the battery temperature sensor.
Resistance in battery circuit
: During the battery capacity check the resistance in the battery circuit is measured. A resistance >
500 mΩ will result in a "Low battery capacity" fault. Checked every 15 minutes.
a) Log on to the c.i.e.
b) Navigate to menu A4.
c) Write control unit number and press
.
d) Please wait.
e) To exit the menu press
or ESC
.
The information is automatically updated every 5th second.
Power supply (control unit xx)
Voltage: xx.xx V
Earth voltage: xx.xx V
Current from power supply: xxx mA
Battery
Voltage: xx.xx V
Charging current: x mA
Temperature xx°C
Resistance in battery circuit: xxxxx mΩ