34.3. CLEAR WEEKLY AVERAGE (H8/S3)
Valid only for 430x, 4400 and 4401 sensors in NORMAL mode: If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be cleared and set to the default value (i.e. "1" = 0.1 %/m), other
-
wise the new / clean sensor will inherit the old sensor's value. It is possible to clear the week average sensor value for each sensor
individually via this menu.
The first week average sensor value (after clearing) will be calculated within one hour, then each week.
a) Log on to the c.i.e.
b) Navigate to menu S3.
c) Write the wanted zone and address and press
.
First replace the sensor and then clear the week average value as soon as possible. Authorised service
personnel only, must do this. Used incorrectly it can cause nuisance fire alarms.
d) To exit the menu press ESC
.
Clear weekly average zone:
0
00 address: 00
(press
↵)