EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
12
4. EBL512 G3
EACH CONTROL UNIT HAS THE FOLLOWING BASIC CONFIGURATION:
For drawings and connection diagram, see Technical description for the c.i.e.
• Grey metal cabinet
-
DIN rail for Gateway (5088)
• MMI board (5015) (Not in 5001S)
-
EBL512 G3 front with display (not in 5001S)
• Main board (5012)
-
Four COM loops (0-3) to which the loop units are connected
-
Four programmable supervised voltage outputs (S0-S3)
-
Two programmable relay outputs (R0-R1)
-
Four programmable supervised / not supervised inputs (I0-I3).
-
Six 24 V DC outputs (power supply outputs for RS485 for redundancy, routing equipment and external equipment)
-
Two not programmable relay outputs for routing equipment (Fire alarm output for Fire brigade tx and Fault condition output
for Fault tx)
-
Connectors for two network boards (5040, 5090)
-
One RS485 and 24 V DC outputs for Display units (5054 V3)
-
One RS485 for redundancy
-
Connector for expansion boards (4580, 4581 & 4583)
-
Connectors for Gateway.
-
Battery charger
-
Connectors for power supply (rectifier) and batteries
-
Connectors for four COM loop boards 5017
• Built-in power supply
-
Switched power supply (rectifier), 230 V AC / 24 V DC (LS150-24/PAN)
-
Space and connection cables for two Sealed Lead-Acid backup batteries (12 V, 28 Ah)
-
Batter temperature sensor
• Space for up to six expansion boards 458x
The control unit can be configured for up to 128, 256 or 512 alarm points. Normally this is factory set but
can be upgraded on site (via EBLWin). This action requires a special download password.
1) EBLG3 Control Unit 5000
2) EBL G3 Control Unit 5001