EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
124
34.8. ACTIVATE / RESET OUTPUTS (H8/S8)
Via this menu, a loop unit output, control unit output and expansion board output can be activated and reset.
Any output can be activated, which means the function can be tested. (Can also be done via EBLWin.)
This is including Addressable siren 4477, Addressable sounder base 3379 / 4479, wireless detector 4611, light indicator 4383, and
all alarm devices 4480, 4481, 4482, 4487.
The selected output will be activated no matter if the control expression is true or not. The selected output will be reset only if the
control expression is false. If the control expression is true when you reset the output via menu H8/S8, the output will remain activat
-
ed until the control expression is false again.
a) Log on to the c.i.e.
b) Navigate to menu S8.
c) Use the soft key "Change type of output" to toggle between:
- Loop unit output
- Control unit output (S0-S3 and R0-R1)
- Exp. board output
d) Write the technical number of the loop unit and press
to activate. Indicated by "√" and a beep.
RESET
e) Use the soft key
to toggle between:
- Activate
- Reset list.
f) Select an item in the reset list and press
. The reset output will disappear from the list, indicated with a beep.
g) To exit the menu press ESC
.
h) Press ESC to leave this menu.
Change type
of unit
Activate
Loop unit
0
00000 output 0