EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
126
35.2. ACTIVATE / DEACTIVATE INTERLOCKING OUTPUT (H9/C2)
The output in each interlocking combination (area / point) can be manually activated via this menu. The corresponding interlocking
input will be "monitored" in the same way as if the output was activated by its control expression.
The output in each interlocking combination (area / point) can be manually deactivated via this menu.
The output will be deactivated also if its control expression still is true and cannot be activated again until
after its control expression has been false again.
Also a latched output will be deactivated. If an interlocking output is activated via its control expression and with latching output
selected (in EBLWin), the output must be deactivated via this menu.
a) Log on to the c.i.e.
b) Navigate to menu C2.
c) Write the area number and address and press
to activate. Indicated by "√" and a beep. The output will directly be shown
in the Deactivate list.
d) Press
to start the alarm mode of this zone address.
DEACTIVATE
e) Use the soft key
to toggle between
- Activate
- Deactivate list.
f) Select an item in the re-connect list and press
. The deactivated output will disappear from the list, indicated with a beep.
g) To exit the menu press ESC
.
Activate
Interlocking output area: 001 point: 01
√
-- Deactivate list (1) -------------------------------------
---------
Interlocking output area: 001 point: 01