EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
15
5.3.1. LED INDICATORS
5.3. DETAILED DESCRIPTION OF THE FRONT
.
1
Fire
Fire alarms. See 18 ALARM
2
Extinguishing
Output(s) for extinguishing equipment activated. (Or a programmable input type "Extinguishing" is
activated.)
3
Ventilation
Output(s) for fire/smoke ventilation equipment activated. (Or
a programmable input type "Ventilation" is activated.)
4
Fire brigade tx
Output "Fire alarm" for fire brigade tx (routing equipment) activated.
Or a programmable input type "Activated routing equipment" is activated. Or test of routing equipment
in progress. See menu 27. PERFORM MONTHLY TEST (H1) on page 87
5
Operation
Steady light: C.i.e. is powered via the rectifier and/or the battery.
Flashing light: C.i.e start up, and if loops are disconnected at start up, until the loops are re-connected.
6
Alarms queued
More than one alarm point / zone have activated fire alarm.
Use push button "Alarms queued" (21) to scroll amongst the alarm points (zone-address) or the soft
key "Next zone" (23) to scroll amongst the zones.
7
System fault
EBL512 G3 is not running because of:
S/W fault
CPU fault
Memory fault
No contact between main board and MMI board
C.i.e. restart (fault code ≠ 00 / 03 /25 / 50 / 53).
8
General fault
Fault(s) in the system.
9
Alarm devices
Steady light: Output(s) type "Alarm device" are disabled.
Flashing light: Output(s) type "Alarm device" have generated fault(s).
This is also valid when the c.i.e. has no "contact" with a unit with such an output, for example 4487,
4479, and so on.
10
Fault tx activated
Not acknowledged fault(s):
Output "Fault condition" for fault tx (routing equipment) is activated.
Test of routing equipment in progress (see menu H1).
Sensitive fault detection mode is on. See menu 31.2. SENSITIVE FAULT DETECTION MODE (H5/A2)
11
Test mode
Zones are in "test mode" (see menu H7).
12
General disablements
Disablement(s) in the system.
13
Fire brigade tx
(Fault/Disablements)
Steady light: Output(s) for "Routing equipment" disabled via menu H2 / B5 or via open door.
Flashing light: Routing equipment power supply outputs or supervised outputs of type "Routing
equipment" have generated fault(s) or the c.i.e. has lost contact with a unit with such an output, for
example 4461.
14
Fire brigade tx delay
The Alert Annunciation function is enabled.