EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
29
11. SILENCE ALARM DEVICES
In the control unit front (the FBP part) there is a push button "Silence alarm devices".
(No.27, see reference
5.3. DETAILED DESCRIPTION OF THE FRONT
When the alarm devices are activated (sounding) and the push button "Silence alarm devices" is pressed, the following will happen:
•
is shown in the display.
The activated outputs programmed for sounders, type "Alarm devices", will be turned OFF (de-activated). This includes Addressable
sounder base 3379 / 4479, Light indicator 4383, Wireless smoke detector 4611, and all alarm devices 448X.
If the push button "Silence alarm devices" is pressed again, the sounders will automatically sound again.
In case of a new alarm the sounders will automatically sound again.
If sounders are programmed with type "Alarm devices for evacuation" they will not be silenced by the
silence alarm devices button.
In EBLWin, the option "Alarm devices doeas not resound for each new alarm" disables alarm devices can be selected.