EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
42
18.1.3. HEAVY SMOKE ALARM / HEAVY HEAT ALARM
An analog detector can activate a heavy smoke / heat alarm for a higher alarm level than the normal fire alarm level, i.e. a normal
fire alarm is already activated by a detector activating a heavy smoke / heat alarm. See EBL512 G3 Planning Instructions for the
system.
Heavy smoke / heat alarm
is to confirm heavy or increasing smoke / heat and can be used for special actions, e.g. activation of
smoke ventilation, and so on.
THE FOLLOWING HAPPENS IN CASE OF A HEAVY SMOKE / HEAT ALARM:
• Outputs programmed for heavy smoke / heat alarm are activated. General heavy smoke / heat alarm and individual alarm
points / zones.
• Each heavy smoke / heat alarm is presented with a "title", which means "Heavy smoke" or "Heavy heat" will be added to the
normal fire alarm information:
** Heavy Smoke **
Zone 002 Address 03
SMOKE
YYYY-MM-DD hh:mm
User definable alarm text
(if programmed)
Menu
002-03
SMOKE
Zone
Address
User definable alarm text for 002-03
Heavy smoke
1 zone in alarm
Alarm number 1 (of 1)
Fire alarm: 002-03
The printer (if available) will print each heavy smoke / heat alarm, and so on:
Heavy smoke / heat alarm will be reset when the fire alarm respectively is reset,
.