EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
43
18.1.4. ALERT ANNUNCIATION ALARM (AA ALARM)
When the AA function is enabled, indicated by the LED Routing equipment "Fire brigade tx delay", the indications, print-outs, actions
and so on are the same as for a normal fire alarm (see above) except for the c.i.e. output for routing equipment (fire brigade tx),
which will not be activated directly.
There will also be a "title". "Alert annunciation" or "Alert annunciation acknowledged" will be added to the normal fire alarm informa
-
tion. The AA alarm has to be acknowledged within an acknowledge time and reset within an investigation time, otherwise the out
-
put(s) for routing equipment (fire brigade tx) will be activated. See EBL512 G3 Planning Instructions for more information regarding
the AA function. Acknowledgement and reset of the AA alarm can be done on an AA unit 5054.
.
Menu
010-01
SMOKE
Zone
Address
User definable alarm text for 010-01
Alert annunciation
1 zone in alarm
Alarm number 1 (of 1)
Fire alarm: 010-01
Ackn. Alert
annunciation
The "Ackn. alert annunciation" text is only visible if an AA alarm is activated and not if this key is used for
the "Evacuate" function.