EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
75
FAULT: Wrong type of unit zone: xxx
address: xx
technical number xxxxxx
Check the type of unit, which should be the same as programmed via EBLWin.
FAULT: Wrong type of unit zone: xxx
address: xx and zone: yyy address: yy
technical number xxxxxx
Check the type of unit (Aspirating smoke detector Aspect Nitro / Grizzle), which should be the same as programmed via EBLWin.
FAULT: Zone line input, Zone xxx Address xx
CU xx expansion board x input x
Valid for the 8 zones exp. board 4580 zone line input x (xxx-xx = zone – address). The board is mounted in control unit xx.
Break on the zone line, wrong / no end-of-line device / short-circuit (if not programmed for fire alarm at short-circuit).
FAULT: Zone line input, zone: xxx address:
xx technical number xxxxxx
Valid for the Multipurpose I/O unit 3361/4461 monitored zone line input Z. Break on the zone line or wrong / no end-of-line
capacitor (10 μF) or short-circuit (if not programmed for fire alarm at short-circuit).
No contact with main board
Shown only in the affected control unit.
• Check that "MMI board" is selected in the SSD (EBLWin, Control unit properties).
• Fault in the Main board software or hardware. Check the cable between the Main board and MMI board. This is a very
serious fault. Call for service personnel/engineer immediately
• In conjunction with SSD download: Erase the SSD in the control unit and download the SSD again.
External fault; User programmable text
Programmable input is connected to any external equipment's fault output. User definable fault message (< 40 characters) has to
be programmed via EBLWin.
The prefix "FAULT:" will not be automatically added.
FAULT: Corrupt program area 2,
Control unit xx
A fault in the control unit xx MMI board. There is some internal fault on the board.
• Try to download S/W again
• Replace the MMI board