EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
91
28.2. OUTPUT (H2/B2)
All programmable outputs in the c.i.e. and outputs in units connected to the COM loops (except outputs of type "Alarm device" or
"Alarm device for evacuation") can be individually disabled.
If you try to disable an output of type "Alarm device" or "Alarm device for evacuation" it will be treated as if it does not exist.
Disabled output: Even if its control expression (trigger condition) is fulfilled (true), the output will not be activated.
DISABLE:
a) Log on to the c.i.e.
b) Navigate to menu B2.
c) Press the soft key
Change type of disablement
to toggle between:
- Loop unit 000000 output 0
- Control unit 00 S0
- Control unit 00 R0
- Control unit 00 expansion board output 0.
d) Type the technical number and output number address.
e) Press
to disable.
RE-ENABLE:
f) Use the
to toggle between:
-
Disable
-
Re-enable list
g) Select “Re-enable list”.
h) Press to select the output that shall be re-enabled.
i) Press
to re-enable.