EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
92
28.3. OUTPUT TYPE (H2/B3)
Via menu B3 outputs of the same type can be collectively disabled in a selected control unit, or in all control units.
Disabled output will stay in (or return to) the normal condition for the output respectively. Disabled outputs are listed in menu H4/U1
from which it is also possible to get a print-out.
DISABLE:
a) Log on to the c.i.e.
b) Navigate to menu B3.
c) Press the soft key
Change type of disablement
to toggle between:
- Control outputs
- Ventilation outputs
- Extinguishing outputs
- Interlocking outputs
d) Type the number of the control unit
e) Press
to disable.
RE-ENABLE:
f) Use the
to toggle between:
- Disable
- Re-enable list
g) Select “Re-enable list”.
h) Press to select the output type that shall be re-enabled.
i) Press
to re-enable.