EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
94
28.6. ALERT ANNUNCIATION (H2/B6)
For alarm points / zones programmed for Alert Annunciation (via EBLWin) is normally the AA function enabled via a time channel, for
example enabled daytime (during working hours) and disabled night time.
As an alternative, the AA function can be continuously enabled (always on).
Via this menu (H2/B6) it is possible to disable the AA function, i.e. the AA function will be turned off for the alarm points / zones
programmed for Alert Annunciation in spite of the time channel is "on" or if they are programmed to be continuously enabled. The AA
function will be turned off until re-enabled via this menu.
DISABLE:
a) Log on to the c.i.e.
b) Navigate to menu B6.
c) By default “Alert annunciation” is selected.
d) Press
to disable.
RE-ENABLE:
e) Use the
to toggle between:
- Disable
- Re-enable list.
f) Select “Re-enable list”.
g) Press
to re-enable.