Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
130
20.1.3
LED indications by inputs
Normally the LED indicators listed below will be lit when a
corresponding output is activated
115
. When selected, the LED will be
turned on when a programmable input is activated instead, e.g. a feed-
back from a fire brigade tx output can activate a programmable input
to turn on the LED "Fire brigade tx".
Fire ventilation activated
: LED "Ventilation"
Extinguishing activated
: LED "Extinguishing"
Routing equipment activated
: LED "Fire brigade tx"
20.1.4
Miscellaneous
Fault latching
(default): all faults, also corrected faults, have to
be acknowledged. No fault latching = not corrected faults have to
be acknowledged but corrected faults have not to be
acknowledged.
NOTE!
In a mixed system (see chapter "Mixed
system, page 14) all control units have to be set to the same.
Pre-warning detection
: The pre-warning detection in a control
unit is enabled as default. When disabled, pre-warnings activated
in other control units in the system will always be presented in all
control units and all programmable outputs in the system, with
trigger condition pre-warning, will be activated (if not disabled).
Fire alarm will always activate all programmable outputs in the
system, with trigger condition pre-warning.
Printer board connected to Main board
: This check box shall
be marked when the c.i.e. has a built-in printer (i.e. an EBL512
G3 unit 5000 with a printer connected to the MMI board).
Suppress buzzer during fault
: This check box shall be marked
when faults generated in other control units shall be suppressed in
this control unit, i.e. the buzzer will only be turned ON for faults
generated in this control unit.
Configured number of addresses
: 128, 256 or 512. Shall be set to
the same as the control unit is configured for.
NOTE!
In a mixed
system (see chapter "Mixed system, page 14) the EBL512 G3 control
unit is configured for max. number of addresses, instead of max.
number of alarm points.
This setting is used when programming alarm points in Win512
version 2.7.x. When doing a validation check you will get a message
if too many alarm points have been programmed in relation to the
settings/configured number of addresses. (This check is automatically
performed when downloading the SSD to the c.i.e.)
115
Type of output = Extinguishing, Fire ventilation and Routing equipment
respectively.