Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
148
25
Current consumption
The different loop units have different current consumption. Note that
some units have much higher current consumption in "active state".
To check the current consumption on the COM loops, cable lengths,
etc. the tables below can be used. See also dwg. 512 G3 - 41 and
chapter "COM loop cable length", page 145. Also, to get a total
current consumption overview and to check if the battery capacity is
enough, the tables below can be used.
The current consumption is normally shown at nominal voltage (24 V
DC), in
Normal state
(quiescent) and in
Alarm state
(active). By
battery back-up (i.e. no mains) the voltage can be 27 – 21 V DC.
See also chapter "Power supply", page 152.
C.i.e. units
Normal state
(quiescent) (mA)
Alarm state
(active) (mA)
Control unit 5000 (
without
printer)
119
230
290
Control unit 5000 (
with
printer)
119
253
312
120
Control unit 5001 ("grey box without front, printer, etc.)
119
179
214
Printer in 5000
23
350
8 zones expansion board 4580
15
121
15
122
8 relays expansion board 4581
15
15
In & outputs expansion board 4583, no units connected
15
15
TLON connection board 1590 / 5090
approx. 5
approx. 5
Web-server II 1598
60
65
The control unit values above are measured during battery back-up
(i.e. no mains).
COM loop units (input / display units)
Normal state
(quiescent) (mA)
Alarm state
(activated) (mA)
119
Control unit – backup battery powered. COM loops and ext. equipment
current consumption not included.
120
When the printer is active the current consumption is 667 mA
momentarily.
121
Add 0.5 mA per input (zone) for end-of-line capacitor (470 nF) and 3 mA
per input for end-of-line resistor (10K).
122
Add 30 mA per input (zone) activated. (Each input has a 30 mA current
limitation, i.e. also for short-circuit on the line.)