Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
36
8
TLON connection board 1590/5090
On the EBL512 G3 control unit (5000 / 5001) main board (5010),
there are spaces and connectors for two TLON connection boards type
1590/5090
20
.
A single (standalone) EBL512 G3 United version 2.7.x control unit is
not possible.
A mixed system, (two or more control units EBL512 version 2.7.x and
EBL512 G3 United version 2.7.x), uses one
single TLON Network
.
Min. one control unit EBL512 version 2.7.x is required in a mixed
system.
The TLON connection board (Network 0) is mounted on the main
board (5010) according to dwg. 512 G3 – 11 and the network is
connected to the terminal block "J4" on main board according to dwg
512 G3 - 24.
8.1
Single TLON Network
In a single TLON Network (Network no. 0), the TLON connection
board (1590/5090) shall be mounted in position no. 0 on the main
board.
8.2
Network programming
The PC program
TLON Manager
is used for the TLON Network
programming.
TLON Manager V1.X
will be replaced with the next
generation
TLON Manager V2.0
.
NOTE!
By the TLON Network programming (installation), some
unique data will be stored in a TLON connection board (1590/5090)
memory and some unique data will be stored in a main board (5010)
memory.
After replacing a TLON connection board only or replacing both a
TLON connection board and a main board, do "Replace" and
"Update" in TLON Manager V2.0.
After replacing a main board to another (not the TLON connection
board), do "Update" in TLON Manager V2.0.
20
TLON connection board type 1590 will be replaced with the next
generation TLON connection board 5090 (which still might be under
development).