Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
63
15.
"Loss of main power source to external power supply equipment"
fault output will activate a fault in the EBL512 system. It will
have the same time delay, as set for the Loss of main power
source fault for the c.i.e. The following fault message will be
shown:
FAULT: Mains, ext. power supply, CU xx
16.
"Loss of the battery charger to external power supply equipment"
fault output will activate a fault in the EBL512 system. It will
have the same time delay, as set for the Loss of main power
source fault for the c.i.e. The following fault message will be
shown:
FAULT: Charging ext. power supply CU xx
17.
When one or more "Fire door closing" outputs are used, these
outputs will be activated for 20 seconds by this trigger condition.
NOTE!
Only valid for inputs and outputs connected to the same
c.i.e.
18.
Pre-warning, e.g. from a High Sensitive Smoke Detector's pre-
warning output. Zone no. and Address set to the same as the
corresponding fire alarm (from the same detector).
19.
Activated input will activate all programmable outputs of type
"Alarm devices" steady (continuous).
20.
Activates any output as long as the input is active.
21.
Input activated when the specified zone has activated fire alarm.
The specified zone is an "extinguishing zone", e.g. a sprinkler
zone. This trigger condition is normally used only for the "New
Zealand indicating panel" in order to control the function of the
key switch "Silence alarms".
25.
The Addressable multipurpose I/O unit 3361 monitored Input 0
used as zone line input (Z) for a single "slave" unit (control unit)
or several control units connected in parallel, see chapter
"Redundancy in distributed system", page 112.
26.
Used for the "outside switch" (i.e. the New Zealand FB Silence
switch).
99.
The Addressable multipurpose I/O unit 3361 monitored Input 0
used as zone line input (Z).
11.2
Logic
The logic has to be set.
51
(•) Normally open / normally low
Normally open contact or
normally low optocoupler input.
( ) Normally closed / normally high
Normally closed contact or
normally high optocoupler input.
51
In the Win512 version 2.7.x dialog box "Input".