EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
103
31. SERVICE (H5)
When commissioning an installation and by maintenance (for example when you power on and when you are programming a control
unit / system), menu H5 can be used for certain actions, information and help.
Only authorized personnel have access to menu H5 and a password for level 3A (Service technician) is required.
a) Log on to the c.i.e.
b) Navigate to menu H5.
c) Press
. A sub menu list (A1 – A9) will be displayed.
Some tasks for Service technicians are done via EBLWin. Via PC and EBLWin you can:
• download / backup (upload) the site specific data (SSD)
• create and download software (S/W), settings, configurations, control unit and system properties.
• create and download the user definable text messages (alarm texts) shown in the display in the control unit and Display units.
To be able to log on to an EBL512 G3 c.i.e. via a PC and EBLWin, the PC has to be provided with an
EBLWin key (5094). This USB device has a number (a key) required for the log on.
Via a PC and TLON Manager you can create and download (install) the TLON network configuration (TLON project).