EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
83
ACTION
DATA deleted
DATA not deleted
RESTART CODE
Power down and then power up again.
(Both mains and battery disconnected)
SSW FFD, WASV
SSD, S/W
SSW*
00 (+50)
Via menu H8/S5 Safe shut down of control unit.
FFD, WASV
SSD, S/W, SSW
00 (+50)
03 (+53)
Via RESET button on Main board. If this reset is done in the middle of a
process, also the SSW might be deleted.
FFD, WASV
SSD, S/W, SSW
00
Via RESET button on MMI board.
SSD S/W, SSW FFD, WASV
50
Reset command via EBLWin or TLON Manager.
FFD, WASV
SSD, S/W, SSW
03 (+53)
Automatically after download of site specific data (SSD) via EBLWin.
FFD, WASV
SSD, S/W, SSW
25
Automatically after download of S/W via EBLWin.
(The old S/W will be deleted.)
FFD, WASV
SSD, S/W, SSW
03 (+53)
Automatically (by the S/W itself) S/W watchdog
FFD, WASV
SSD, S/W, SSW
13
Automatically due to trying to use auto boot mode with a MMI board that
doesn’t support auto boot mode
FFD, WASV
SSD, S/W, SSW
15
Automatically due to some external disturbance.
If this happens, call for service personnel / engineer.
Depending on the restart reason, also the SSW might be deleted.
FFD, WASV
SSD, S/W, SSW
01, 02 alt. 04-12
25.2. RESTART TABLE
Here follows a table describing the different reset alternatives and how the data respectively is affected:
During the restart, the fault output (relay) for the Fault tx will be "activated", the supervised 24 V DC out
-
puts S0-S3 will be not supervised and S0-S3 programmed as normally high will be low for a few seconds.
Code 00 – 49 = Main board restart. Some data might be lost, see above.
Code 50 – 99 = MMI board restart. No data is lost.
* SSW previously saved with safe shut down is not deleted.
25.2.1. EXPLANATION OF RESTART CODES
Code 00 appears after manual power on/off or S/W download.
Code 03 will appear after a normal restart.
Code 13 is always followed by an address, to be noted.
Code 25 appears after download of SSD and automatic restart.
Code 50 will appear only if the c.i.e. has an MMI board.
Code 53 will appear only if the c.i.e. has an MMI board.