Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
108
27.4
Sensor values (H4/U4)
The very first week average sensor value is calculated within 2
minutes after SSD download & restart. During these 2 minutes can no
fire alarm be activated and the sensor value "000" will be shown.
The "Performance factor" and "Min. / Max." values are updated each
night (00:00), i.e. the values shown are from the previous day.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H4.
H4 Present system status
"
↵
"
U1 Disablement
U2 Disablement by time channel
U3 Open doors
U4 Sensor values
U5 Sensors activating SERVICE signal
U6 Event log
U7 Information
Scroll to menu U4.
U4 Sensor values
"
↵
"
Start sensor:
0
00000
Write the technical number
and/or press "
↵
" to start
as from sensor 000001.
"
↵
"
(When "
↵
" is pressed, the sensor values will be shown in the
display. An examples which shows the values from an analog
multi detector 4300 and an analog heat detector 3308:)
Sensor: 001-01 (technical address 000001)
Momentary: XX.X%/m Weekly: XX.X%/m
Perf factor: X.XX%/m Min: XX.X%/m
Algorithm: X-XX Max: XX.X%/m
Momentary: XX°C Min: XX°C
Algorithm: XX Max: XX°C
A list in which you can
scroll with "▼" or "▲".
If printer is mounted the
soft key "Print" will be
visible, else not. Press
"Print" for a print-out.
If there are no sensors
(analog detectors) when
"
↵
" is pressed, the list
view will not open.
Sensor: 001-03 (technical address 000002)
Momentary: XX°C Min: XX°C
Algorithm: XX Max: XX°C
Escape
menu
"
↵
"
Start sensor:
0
00000
Write another technical
number and press "
↵
" or
press "ESC".
"ESC"
U4 Sensor values
Scroll to another menu or
press "
ESC
".