Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
118
28.3
Sensitive fault detection mode (H5/A2)
To increase the possibilities to detect faults during the commissioning,
it is possible to use the "Sensitive fault detection mode". The time
delay for each fault will then be reduced, i.e. you might find some
faults now instead of in the future.
The "Sensitive fault detection mode" turned on is indicated by the
LED
Routing equipment
"Fault tx activated" (L13) and the "Fault"
output for routing equipment is "activated".
NOTE!
Don't forget to turn off this mode after the commissioning.
Action
Text in display
Comments
"Menu"
According to chapter
"Access code for service /
maintenance (H5 and
H8)", see page 116.
"
↵
"
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
Scroll to menu A2
A2 Sensitive fault detection mode
"
↵
"
Sensitive fault detection mode:
Off
On
Press
"
↵
"
to turn off
or
s
elect "On" and press
"
↵
"
to turn on the sensitive
fault detection mode.
"On"
"
↵
"
A2 Sensitive fault detection mode
Scroll to another menu or
press "
ESC
".