Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
127
30
Perform ZONE TEST (Test mode)
(H7)
Normally, zones are tested during the monthly test via menu H1. Via
this menu (H7) it is possible to perform the zone test solely.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S5.)
If a real fire alarm is activated by
an alarm point not in test mode
,
the normal fire alarm functions will be activated, i.e. fire alarm
presentation, outputs (sounders) activated, routing equipment (fire
brigade tx) activated, etc.
See also chapter "The information area priority order", page 22.
NOTE!
If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in WinG3).
There will be an automatic test mode ending one hour after the latest
tested alarm point.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H7.
H7 Perform ZONE TEST
"
↵
"
Zones to be set in test mode:
?
?? ??? ??? ???
Write the zone numbers
(e.g. 001, 002, 003,
004).
Zones to be set in test mode:
001 002 003
4
00
Press "
↵
" to start the test
mode.
"
↵
"
Zones in test mode:
001 002 003 004 End test:
↵
LED "Test mode" (L8)
will light up. Perform the
tests.
The zone(s) will stay in test mode until the test mode is ended
but after 60 minutes or if you press "Esc
menu" you will be logged out from menu H7.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up, and the LEDs "Fire" (L1) in the c.i.e. will light up, approx.
10 seconds, then the alarm point will be automatically reset. The printer, if available, will print out every
tested alarm point (Zone: xxx Address: xx Time: HH.MM).
A sensor in test mode will not be able to activate fault.
After 60 minutes
or
Zones in test mode:
You are no longer in menu