Operating Instructions Fire alarm system EBL512 G3, V1.1.x
131
31.3
Re-connect loop (H8/S2)
Disconnected (disabled) loops / zone lines (via menu H8/S1) are
indicated by LED
Fault / Disablements
"General disablements" (L10)
and listed in menu H4/U1.
NOTE!
When you re-connect a COM loop all the statistics shown in
menu H5/A7 will be erased and set to "0".
When all loops / zone lines have been re-enabled, The LED
Fault /
Disablements
"General disablements" (L10) will be turned OFF, if
there are no other disablements in the system.
Action
Text in display
Comments
"Menu"
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
"
↵
"
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
Scroll to menu S2.
S2 Re-connect loop
"
↵
"
Re-connect type:
COM-loop
Zone line input
Addr zone interface
Use
"▲" or "▼" to
select a type and press
"
↵
".
"
↵
"
Depending on the
selected type, the
following will be
shown:
Re-enable COM-loop:
0
, control unit: 00
Write the required data and
press "
↲
".
Re-enable zone line input
Zone line input:
0
, exp board: 0, control unit: 00
Re-enable addressable zone interface
Input technical number:
0
00000
"
↲
"
Re-connect type:
COM-loop
Zone line input
Addr zone interface
Continue to re-connect or
press "ESC" to menu S2.
"ESC
S2 Re-connect loop
Scroll to another menu or
press "
ESC
".