Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
139
31.8
Activate address in alarm mode (H8/S7)
One alarm point (zone-address), not a whole zone, can be set in alarm.
The built-in LED in the alarm point (detector) will be turned on to
indicate the alarm.
NOTE!
All outputs, standard and programmable, which would have
been activated by a real fire alarm from the same alarm point, will
now also be activated.
Action
Text in display
Comments
"Menu"
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
"
↵
"
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
Scroll to menu S7.
S7 Activate address in alarm mode
"
↲
"
Select zone:
0
00 address: 00
(press
↵
)
Write the zone number and
address (e.g. 123-45).
Press "
↲
" to start the fire
alarm.