Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
32
10
"Silence buzzer"
The
buzzer
in the control unit will sound for:
Fire alarm
11
(0.4 / 0.4 sec.)
Co-incidence alarm (2-zone or 2-unit dependent fire alarm):
When only one
zone
or one
zone / address
(alarm point) is in
alarm status (0.8 / 5 sec.)
Pre-warning (0.8 / 5 sec.)
Quiet alarm (0.8 / 5 sec.)
Fault (continuous)
Disablements and Faults (1 sec. directly after the door to the c.i.e.
is closed.)
Activated interlocking input (0.8 / 0.8 sec.), if this option is
selected via WinG3.
Press "Silence buzzer"
(P1)
to silence the buzzer.
In case of a new alarm (pre-warning, co-incidence alarm, etc.) or if the
push button "Silence buzzer" is pressed again, the buzzer will
automatically sound again.
Silence buzzer by open door
In WinG3 can the function "Silence Buzzer by Door Switch" be
selected. The buzzer will then be turned off as long as the control unit
door is open. (This function is a violation to the EN54-2 standard.)
EBL512 G3 c.i.e. type no. 5001
This unit has no front and no built-in buzzer.
11
Incl. Heavy smoke/heat alarm, AA alarm, Key cabinet alarm and
Acknowledged alarm (New Zealand only).