Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
65
There will also be a "FAULT: No reply ….." message for each unit
not found by the c.i.e.
If there are several short-circuits on the loop the message shows the
isolator just before the break in the A-direction (incl. the following
isolator). There will also be shown "
FAULT: Multiple
faults
…".
NOTE!
Each 10
th
minute a check is performed if all short-circuits are
corrected (repaired). If so, the communication automatically returns
to communicate in the A-direction only.
29
FAULT: Site specific data (SSD),
control unit xx
The Site Specific Data (SSD) in control unit no. xx is not downloaded
correctly (a checksum fault, etc.). A new SSD download (via WinG3)
is required.
FAULT: Site specific data, alert
annunciation unit xx, control unit xx
FAULT: Site specific data, external
presentation unit xx, control unit xx
FAULT: Site specific data, fire brigade
panel xx, control unit xx
Alert Annunciation Unit 1735 / 1736 .
Ext. Presentation Unit 1728.
Ext. Fire Brigade Panel 1826 / 1828.
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Supervised input x, control unit xx
A fault on the supervised input x in control unit xx.
Check the cables / connections (cut-off or short-circuit).
FAULT: Supervised input x expansion board
x,
control unit xx
29
NOTE!
The fault has to be acknowledged, i.e. and it can last up to 10
minutes after the acknowledgement before the communication returns to
communicate in the A-direction only.