Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
66
A fault on the supervised input x on the expansion board 4583 with
address x, in control unit no. xx.
Check the cables / connections (cut-off or short-circuit).
FAULT: Supervised output x,
control unit xx
If the output is programmed for sounders (type "Alarm devices"), it is
also indicated by LED
Fault / Disablements
"Alarm devices" (L11)
blinking.
If the output is programmed for fire brigade tx (type "Routing
equipment"), it is also indicated by LED
Fault / Disablements
"Fire
brigade tx" (L12) blinking.
If the output is programmed for an extinguishing system (type
"Extinguishing"), there will be an additional information text close to
the soft key area in the display:
Extinguishing wire fault
.
x=0
(S0): Short circuit/break on the connected cable/ equipment
and/or blown fuse F4 on the main board 5010.
x=1
(S1): Short circuit/break on the connected cable/ equipment
and/or blown fuse F5 on the main board 5010.
x=2
(S2): Short circuit/break on the connected cable/ equipment
and/or blown fuse F6 on the main board 5010.
x=3
(S3): Short circuit/break on the connected cable/ equipment
and/or blown fuse F7 on the main board 5010.
Fuse T
500mA
L 250V (TR5).
Calibration not performed via menu H5/A1.
Connected equipment might be "stolen".
Resistor(s) missing or not correct value. (1-5 resistors
33K)
NOTE!
The calibrated value has to be in the range 4K7-50K.
FAULT: Supervised output x expansion board
x, control unit xx
A fault on the supervised output x on the expansion board 4583 with
address x, in control unit no. xx.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED
Fault / Disablements
"Alarm devices" (L11)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED
Fault / Disablements
"Fire
brigade tx" (L12) blinking.
Calibration not performed via menu H5/A1.
Short-circuit / break on the connected cable / equipment.
Blown fuse F1 (Output 0) or F2 (Output 1) on the 4583
board. Fuse T
200mA
L 250V (TR5).