1-1-1-1-7
1
Twin-Type
1-1. Unit Specifications
PZH2
4-Way Cassette Type S-125PU2E5B ×2 / U-250PZH2E8
INDOOR
MODEL
S-125PU2E5B ×2
-
-
PANEL
MODEL
Standard type:CZ-KPU3 / ECONAVI type:CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-250PZH2E8
-
Branch pipe
MODEL
CZ-P680BK2
Performance test condition
ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz
1Ø 50Hz
3Ø 50Hz
V
220V
230V
240V
380V
400V
415V
Min
Max
C
O
O
L
I
N
G
Capacity
kW
25.0
25.0
25.0
-
-
-
6.1
28.0
BTU/h
85300
85300
85300
-
-
-
20800
95500
Current
A
0.91 ×2
0.88 ×2
0.85 ×2
12.8
12.1
11.7
-
-
Input power
W
110 ×2
110 ×2
110 ×2
7.840k
7.840k
7.840k
-
-
TOTAL W
-
8.060k
8.060k
8.060k
1.200k
9.720k
Annual consumption
TOTAL kWh *
4
-
-
-
-
4030
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.10
3.10 /B
3.10
5.08
2.88
Erp
*
6
Pdesign
kW
-
-
-
-
25.0
-
-
-
η
s,c
(W/W)
-
-
-
-
296.2
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
93
93
-
-
Noise indoor *
7
dB-A (H/M/L)
46/39/33
-
-
-
Power Level dB
61/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
59/-
-
-
Power Level dB
-
78/-
-
-
H
E
A
T
I
N
G
Capacity
kW
28.0
28.0
28.0
-
-
-
5.5
31.5
BTU/h
95500
95500
95500
-
-
-
18800
107500
Current
A
0.90 ×2
0.87 ×2
0.84 ×2
11.4
10.8
10.4
-
-
Input power
W
105 ×2
105 ×2
105 ×2
6.990k
6.990k
6.990k
-
-
TOTAL W
-
7.200k
7.200k
7.200k
1.000k
10.100k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.89
3.89 /A
3.89
5.50
3.12
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
20.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
η
s,h
(W/W)
-
-
-
-
174.1
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.00
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
93
93
-
-
Noise indoor *
7
dB-A (H/M/L)
46/39/33
-
-
-
Power Level dB
61/54/48
-
-
-
Noise outdoor
dB-A (H/L)
-
63/-
-
-
Power Level dB
-
82/-
-
-
EXTRA LOW TEMP Total capacity(kW)/Input power(W)/COP
-
-
Max Current(A) / Max Input power(W)
0.91/110 ×2 0.88/110 ×2 0.85/110 ×2
18.5/11.3k
18.5/11.9k
18.5/12.4k
-
Starting current(A) (Cooling/Heating)
-
-
-
12.8/11.4
12.1/10.8
11.7/10.4
-
Comp output(W)
-
5.50k
5.50k
5.50k
-
Time Delay fuse max size(A)
5
30
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
90
120 × 2
-
Moisture removal volume
L/h(Pt/h)
9.6 (4.8 ×2) (20.2)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m
3
/min (m
3
/h) (H/M/L) 37.0×2/27.0×2/19.0×2 (2220)×2/(1620)×2/(1140)×2
-
-
-
Heating
m
3
/min (m
3
/h) (H/M/L) 37.0×2/27.0×2/19.0×2 (2220)×2/(1620)×2/(1140)×2
-
-
-
Outdoor
Air flow
Cooling
m
3
/min (m
3
/h)
-
160.0 (9600)
-
-
Heating
m
3
/min (m
3
/h)
-
160.0 (9600)
-
-
Refrigerant type / amount
g
(oz)
-
R32 5.20k (183.4)
-
Product dimension
Height mm(inch)
319
(12-9/16)
1500
(59-1/16)
-
Width mm(inch)
840
(33-5/64)
980
(38-37/64)
-
Depth mm(inch)
840
(33-5/64)
370
(14-9/16)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
(1-11/32×37-13/32×37-13/32)
-
-
Packing dimension
Height mm(inch)
365
(14-3/8)
1642
(64-41/64)
-
Width mm(inch)
898
(35-3/8)
1095
(43-7/64)
-
Depth mm(inch)
898
(35-3/8)
529
(20-53/64)
-
Weight
(NET)
k
g
(lb)
25
(55)
128
(282)
-
(GROSS) k
g
(lb)
32
(71)
140
(309)
-
Panel (NET) k
g
(lb)
5
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
(Liquid)Ø12.7(1/2) (Gas)Ø25.4(1)
-
Connecting method
flared type
(Liquid)flared type (Gas)brazing connection
-
Standard length m(ft)
7.5 (24.6)
-
Pipe length range m (ft)
5 ~ 60 m (16.4 ~ 196.9)
-
Indoor unit & Outdoor unit height difference m (ft)
30 m(OD located lower) / 30 m(OD located higher) (98.4 / 98.4)
-
Add gas amount
g
/m (oz/ft)
80
g
/m (0.860)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 η
s,c
and η
s,h
classification is at 230V(400V) only in accordance with EN-14825. For heating, η
s,h
indicates the value of only Average heating season.
*7 H:High at setting 5 stage (Level 5), M:Middle at setting 5 stage (Level 3), L:Low at setting 5 stage (Level 1)
SM830276-00_欧州向け R32シングル TD&SM.indb 7
2019/02/27 11:54:11
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...