5-6
5
Symptoms and Parts to Inspect
Remote
controller
alarm display
Alarm
contents
Judgement conditions
Eliminating
condition of alarm
Judgement and correction
P03
Abnormal discharge
temperature error
• Discharge temp.
detected at or
above the specified
value
Stops when temp. exceeds
101 .
Alarm output on 5 pre-trips
1. Check refrigerant cycle (gas
leak).
2.Trouble with electronic
expansion valve
3.Check discharge
temperature sensor (TD).
P05
CT disconnected
or AC power supply
error
DC voltage charge
failure
The current value transmitted
from the microcomputer on the
outdoor unit control substrate is
low.
When no AC power input for
more than 30 seconds to 5
minutes : Single alarm
Check outdoor unit control
PCB.
1.
2. Lack of reactor wire
3. Check power frequency.
P15
Insufficient gas level
detected.
• Discharge temperature is 95
or higher.
• Electronic expansion valve is at
Step 480.
1.Check refrigerant cycle (gas
leak).
2.Trouble with electronic
expansion valve
3.Check outdoor unit valve
opening.
L18
4-way valve
operation failure
• Judged after heating
operating for
5 minutes
consecutively.
The indoor unit heat exchanger
temperature drops even though
the compressor is switched on
during the heating mode:
To +20
Pre-trip 1 time
1. Check 4-way valve.
2. Check 4-way valve wiring.
3. Check outdoor unit control
PCB.
P04
P22
P29
H31
High-pressure
protection error
High pressure switched
ON
(Alarm is output when switch
opened.) Pre-trip 4 times.
OFF
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
Overload operation of
refrigerant cycle
Outdoor unit fan
motor trouble
• Inverter protection
circuit was
activated, or lock
was detected at
outdoor unit fan
motor.
Inverter stops after alarm is
detected. Pre-trip 10 times
1.Position detection trouble.
2.Outdoor unit fan motor over-
current Protection circuit is
activated.
• Check outdoor unit control
PCB.
• Refer to outdoor unit fan
judgement methods.
Lack of INV
compressor wiring,
INV compressor
actuation failure,
DCCT failure
HIC trouble
Inverter stops after alarm
is detected. Alarm is output
when inverter stops (pre-trip)
consecutively 10 times.
Pre-trip consecutively 10 times
Recovery at restart
Temperature dropped
1.Stops immediately even
when operations restarted.
• Layer short on the
compressor
2.Check HIC circuit.
• Wiring trouble
Heat sink and PCB (HIC)
• Contact trouble
When the above has continued
for 1 minute. Indoor air sucking
due to body thermostat max
• Secondary current ≤ Current
value of gas shortage
determination
(E1 or E2) - TA < 4
< C1
SM830276-00_欧州向け R32シングル TD&SM.indb 6
19/02/28 13:29:13
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...