5-10
5
E15 Automatic Address Alarm (The total capacity of indoor units is too low.)
Error Detection Method
It is judged an error the total capacity of indoor units replied by communication is lower than that of outdoor unit.
Connecting indoor unit
The total capacity of indoor units is lower than that of outdoor unit.
•
Some indoor unit(s) are connected but power is not turned on.
•
The CHK pin (CN062/CN071) and/or TEST pin (CN064) of the indoor unit is shorted when its power is turned on.
•
High voltage was applied (over AC200V) in the indoor/outdoor operations line circuit.
•
1.
Is the indoor unit powered off?
1-1
Was the number of indoor units changed after auto address setting
finished?
3-1
Conduct checks prior to auto address setting.
3-2
3-2
3-1
Yes
No
Power on
2-1
Yes
No
Was a high voltage (over AC200V) applied in the indoor/outdoor
operations line circuit?
2-2
2
Is the indoor/outdoor control line opened or shorted?
2-1
Correct the wiring
2-2
Yes
No
Indoor/
outdoor
control line
3 No. of
Indoor
Units
1 Power
Source
Error Diagnosis
2.
3-2
4-1
Yes
No
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board and see whether the E15 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
Replace wireless remote control parts including wiring.
4-3
4-4
Is the LED blinking on the indoor unit’s control PC board?
4-5
Check all items under the section “Check Prior to Auto Address Setting”.
5-1
The nonvolatile memory (EEPROM) on the indoor unit’s control board is either not installed,
improperly installed or the nonvolatile memory is faulty. Correct this or after replacing the
nonvolatile memory, write model data to it in the remote control detailed settings mode.
4-6
Are the CHK pin and TEST pin on the indoor unit control board
short-circuited?
4-1
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
4-2
4-4
4-5
Yes
No
Remove the short
4-2
Yes
No
4-3
4-5
Yes
No
4 Indoor
unit
control
PC board
5 Outdoor
unit control
PC board
4-6
5-1
Yes
No
For information on the remote control’s detailed settings, refer to the Reference Materials.
•
For information on the procedures for replacing the nonvolatile memory (EEPROM) of the indoor unit, refer to the manual
that is packaged with the indoor unit service board.
•
OPTION (CN060)
T10 (CN061)
CHK (CN062)
DISP
FAN DRIVE (CN032)
JP001
POWER LED (D002)
EXCT (CN073)
RC
EEPROM (IC010)
Indoor Unit Control PCB (ACXA73-3081*)
: S-200PE3E5B, S-250PE3E5B
Indoor Unit Control PCB (ACXA73-2553*)
: S-50PU2E5B, S-60PU2E5B, S-71PU2E5B, S-100PU2E5B,
S-125PU2E5B
POWER LED (D002)
EEPROM (IC010)
EMG (CN044) OC (CN040)
DISP (CN063)
CHK (CN062) T10 (CN061)
EXCT (CN073)
JP001
FAN DRIVE (CN032)
SM830276-00_欧州向け R32シングル TD&SM.indb 10
19/02/28 13:29:23
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...