6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History
* Displays outdoor unit alarms only. Does not display indoor unit alarms.
* Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device.
(3)
(2)
(1)
(4)
(5)
A
<Operating procedure>
(1) Press and hold the
(Check) button and
button simultaneously for 4 seconds or longer to engage
outdoor unit alarm history mode.
During temperature monitoring, illuminates.
The display and operations are the same as for the
alarm history monitor performed from the indoor unit
remote controller. However the “UNIT No.” display shows
the outdoor unit address.
(2) Press the
button and select the outdoor unit for
which to monitor the alarm history.
(3) Press the temperature setting
and
buttons and
select the item code for the alarm history.
The select outdoor unit address, the item code, and the
alarm history (alarm data) are displayed.
The outdoor unit address is displayed as R.C. XX-YY.
System XX = Outdoor unit system address
R.C. XX = Outdoor unit system address
YY = Outdoor unit sub-bus address
Item codes 01-08 are displayed. 01 indicates the most
recent alarm.
The alarm history displays the alarm code. (If no alarm
are present, then -- -- is displayed.)
(4) To clear the alarm history, press the
button. (The
outdoor unit alarm history will be cleared.)
(5) To exit, press the
(Check) button. The display
returns to the normal display.
2WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
6. Mode Settings
Press and hold the
(1)
(2)
(Check) button and
(Ventilation) button simultaneously for 4
seconds or longer.
Press the temperature setting
and
buttons to change the item code. The item codes
and setting data are shown on the next page.
Press the timer time
buttons to
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “ ” display stops blinking
and remains lit.)
During this mode, “ ” is displayed,
blinking. The outdoor unit address display section
displays “ALL,” the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. (C)).
and the last 3 digits (Fig. (D)).
(D)
(C) and (D) are displayed alternately.
(C)
When the first 3 digits are displayed, the bottom dot
of the colon is illuminated.)
To exit the setting mode, press the
(Check)
button.
(2)
(5)
(1)
(Example shows display of 000 001.)
Display of fi rst 3 digits
Display of last 3 digits
(3)
(4)
(5)
and
(3)
(2)
(5)
(1)
(3)
A
A
SM830276-00_欧州向け R32シングル TD&SM.indb 10
19/02/12 15:38:58
Summary of Contents for Elite Big PAC-i S-200PE3E5B
Page 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Page 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Page 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Page 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Page 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Page 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...