Installation, Use and Maintenance Manual - ERV+DX series
page 21
En
g
lis
h
SECtIoN 1 - gENEral CharaCtErIStICS
1.1 Presentation of the manual
This manual describes the rules for the transportation, the installation, the use and the maintenance of the heat recovery. The user will find every-
thing that is normally useful to know for a correct and safe installation of the ERV+DX unit.
The non-observance of what is described in this handbook and an inadequate installation of the ERV+DX unit may cause the cancellation of the
guarantee that the Manufacturer/Distributor Company grants on the same one. The Manufacturer/distributor Company, moreover, does not
answer to possible direct and/or indirect damages due to wrong installation carried out by inexpert and/or non-authorised staff. At the moment of
the purchase, check that the machine is integral and complete. Claims will have to be produced within 8 days from the reception of the goods.
1.2 general characteristics
• Galvanized steel self-supporting panels, internally and externally insulated
• Counterflow air-to-air heat recovery device, made of plane sheets of special paper with special sealing to keep airflows separate and only
permeable to water vapor.
total heat exchange
with temperature efficiency up to 77% and enthalpy efficiency up to 63%, also at high level
during summer season
• G4 efficiency class filters with synthetic cleanable media, both on fresh air and return air intake
• Removable side panel to access filters and heat recovery in the event of scheduled maintenance
• Motorised heat recovery by-pass device automatically controlled by unit control to use fresh air free-cooling when convenient
•
Low consumption
, high efficiency & low noise direct driven fans with 3-speed
EC motors
•
Supply section complete with DX coil
(R410A) fitted with solenoid control valve, freon filter, contact temperature sensors on liquid and gas
line, NTC sensors upstream and downstream airflow
•
Purifying system Bioxigen
®
, switched on at fans running, able to do an efficient antibacterial treatment, ensuring a perfect healthiness of sup-
plied air
• Built-in electric box equipped with PCB to control internal fan speed and to interconnect outdoor/indoor units
• Duct connection by circular plastic collars
1.3 Erv+DX series technical data
moDEl Erv+DX
Nominal airflow rate
High speed
Med speed
Low speed
Nominal E.S.P.
High speed
Med speed
Low speed
1,5 m sound pressure level
High speed
Med speed
Low speed
Power supply
Max current
Max power input
hEat rECovEry
Winter mode
(1)
Temperature efficiency
Enthalpy efficiency
Saved power
Summer mode
(2)
Temperature efficiency
Enthalpy efficiency
Saved power
DX CoIl
heating mode
Total capacity
Off temperature
Off R.H.
Cooling mode
Total capacity
Sensible capacity
Off temperature
Off R.H.
PaW-500zDX2 PaW-800zDX2 PaW-01KzDX2
m
3
/h
500
800
1000
500
800
780
360
625
650
Pa
85
117
104
45
68
69
21
18
17
dB (A)
33
38
39
31
36
37
27
32
33
V/ph/Hz
230/1/50
A
1,1
2,3
2,5
W
135
300
310
%
76,5 (76,5)
73 (73)
73,5 (73,5)
62,3 (64,1)
59 (60,8)
59,5 (61,2)
W
4,3 (4,8)
6,5 (7,3)
8,2 (9,0)
%
62,5
59
59,5
60
57
57,5
W
1,7
2,5
3,2
kW
2,9 (3,1)
4,0 (4,3)
4,6 (5,0)
°C
30,1 (29,2)
27,5 (26,5)
26,3 (25,3)
%
16 (15)
18 (17)
19 (18)
kW
3,0
4,0
4,5
kW
2,0
2,8
3,3
°C
16,5
17,9
18,6
%
86
82
81
(1) Nominal winter conditions: outside air: -5°C (-10°C) DB, RH 80%
ambient air: 20°C DB, RH 50%
(2) Nominal summer conditions: outside air: 32°C DB, RH 50%
ambient air: 26°C DB, RH 50%
DC MAN I 00 ERVDX 01 - Man. Inst. CFR microDX - Panasonic_SIC 11/10/2013 8.20 Pagina 21