● At least once a year, please do self-inspection due to safety check sheet. If any abnormality occurs, immediately  contact  electrical worker.
● Receive the check by the specialist in the construction shop etc. once every three years.
● when will use beyond 10 years after installation, At least once a year, please do inspection due et. At least once a year at least, please accept 

inspection by a electrical worker to be sure. and  When it passes for 15 years after installation, Please stop use promptly and exchange it.

■ Safety Check Sheet (Self-check):

At least once a year

Safety Check Sheet & Maintenance Sheet

Contents of inspection

Result

Duration 

of use

1

Less than 10 years of use?
More than 15 years of use?

conditions of use

1

Are there condense on the ducts?

2

Are there stains or discoloration on 

the inside of the duct?

3

Are there deposits of dust adhering 

to the inside of the duct?

4

Are there an abnormal looseness or 

gap?

5

Are the connection parts of duct 

straight ?

6

Are there such a strange odor or 

smell burnt?

Contents of inspection

Result

conditions

 of use

7

Did blocked the earth leakage breakers?

8

Had the power supply of the apparatus 

linked to a duct turned on and off ?

A title

Check 

day

   Y  D  M 

The check 

person in charge 

Result

○:Normal

Measures

○:Exchange required

●:Finished with exchange

×:Abnormality

△:Adjustment  required

▲:Finished with adjustment 

A title

Contents of inspection

Remedy

Result

Measures

Duct

Is there condensation?

Eliminate the cause of condensation

Mount the duct to the ceiling side directly, Are there 
loose the screw?

Retighten

Are there discoloration or deformation in the plastic 
of the duct and 

Change it.

Are there adhesion and deposition of dust in the inside of a duct? Remove the dirt

Is a straight line connecting duct?

Attachment  is  improved  so  that  it  may  become  a 
straight line.

Is the thing which is not an exclusive plug attached to the duct? Exchange plugs.

 The parts to 

connect

・feed-in cap
・Center-feed-in joiner
・Joiner
・Joiner L
・End cap

Are there any slack of a set screw ?

Retighten

Is the duct  insufficient to merge ?

Iserts enough to the back.

Is cover detached?

Replace the cover

Are there discoloration or deformation in the plastic? Change it.
Are there breakage and a crack?

Change it.

Are there loose the terminal screw?

Retighten

Plug

Correct direction of the attachment to the duct?

Attach after checking direction.

Are there loose the terminal screw?

Retighten

Is the plastic of the plug discoloring and changing?

Change it.

Are there breakage and a crack?

Change it.

Is the electric wire of the plug pulled?

takes a little longer

Hanger

Are there loose hanger nat?

Retighten

Are there loose hanger cap?

Turns to the right until it locks.

 All

Insulation resistance: 0.1 M Ω or more
 voltage to ground 150 V or less

Do  pertain  to  your  particular  place  and  cause 
abnormal

Caution

● Action against abnormal, turn off the power 

before, checks by the  electrical worker.

Not doing so will result in an electric shock, a fire, or a 
drop.

2.Where to Find 

  discoloration

Duct

Where to Find:
The plastic part near 
the conductor
(Conductor : 2 parts)
※ Gray area

■Maintenance Sheet(The contents of check by electrical worker)

 : 

Least once every three years during and after completion

3

Summary of Contents for Factory Line 20

Page 1: ...your electrical worker to take necessary actions In such case be sure to pass Instruction and Installation Manuals Not doing so will result in an electric shock a fire or a drop Use the rated voltage within the load capacity that is always displayed Not doing so will result in a fire Use Fluorescent lighting plug below a permissible load Not doing so will result in a fire or a drop Caution this pr...

Page 2: ...he smoke rises The place which is subject to the influence of heat such as the upper part of a heater Not doing so will result in an electric shock a fire or a drop Do not install the Factory Line duct passing through building structure Doing so may result in a fire Do not slide putting the plug in the duct Poor contact will cause a fire During construction Do not give a shock such as dropping on ...

Page 3: ...ceiling side directly Are there loose the screw Retighten Are there discoloration or deformation in the plastic of the duct and Change it Are there adhesion and deposition of dust in the inside of a duct Remove the dirt Is a straight line connecting duct Attachment is improved so that it may become a straight line Is the thing which is not an exclusive plug attached to the duct Exchange plugs The ...

Page 4: ... mm mount the flange and then mount a pipe to the flange Unit mm Mounting the ducts directly to the ceiling Support spacing for the duct 1 Turn the flange cover to the left to remove it 2 Use the wood screw or tapping screw then mount the flange to a structural member 3 Align the pipe mounting hole of the pipe suspension hanger with the position of the pan head machine screw to put the pipe in the...

Page 5: ...via the pipe suspended hangers method for bringing in the power supply Route the cable from the ceiling into the pipe When doing this it is easier if the cable is passed through the pipe before securing the Factory Line 20 duct in the hanger Following the same procedure for Step fit the duct in the hanger and then fix it with the cap Use single conductor cables of 1 6 or 2 0 m in size Make wire co...

Page 6: ... duct into the hanger and then turn the cap to the right and tighten the securing screw in order to secure the duct Ensure the strength of building structures enough to support the hanging weight a maximum of 10 kg per support Not doing so may cause the hanger to drop To use long hanger bolts mount these bolts using sway braces Use two or more pieces of hanger for one duct It will become a cause o...

Page 7: ...rew During construction Do not give a shock such as dropping on a product or hitting It may be damaged Combine the tip of a duct and connect certainly Connect a straightly both of the duct Securely fasten the set screws Proper torque 0 98 N m 1 32 N m Doing so may result in an electric shock or a fire When cutting the ducts use a metal hacksaw hand type and cut with the opening in the duct facing d...

Page 8: ...y cable of the grounded side to the Polarity indication ground side the terminal screw of which is plated Caution Set screw Polarity indication ground side Polarity indication ground side Duct Duct Grund terminal M4 Terminal screw plated To connect the duct with the center feed in joiner be sure to align the Polarity indication ground side with each other Only to make connection the cover needs no...

Page 9: ...ng so may result in a fire Do not slide the plug with having come in the duct Doing so may result in faulty connection thus leading to a fire Caution Notes Do not attach the plug unit where the tapping screw is used the duct directiy Notes Do not attach the plug unit where the tapping screw is used the duct directiy 1 2 3 4 5 Do not slide the plug with having come in the duct Doing so may result in ...

Page 10: ...g the lever duct outlet plug lever lock Notes Do not attach the plug unit where the tapping screw is used the duct directiy Do not slide the plug with having come in the duct Doing so may result in faulty connection thus leading to a fire Caution 13 Mounting an electrical outlet plug Mounting plug Matching the polarity indications on the duct and the plug insert the plug into the duct and rotate it...

Page 11: ...ut Fluorescent lighting plug Power supply hole Locknut Mounting fluorescent lighting fixture to the duct fluorescent lighting plug and clamp lever handling method To mount Rotate clockwise until the lever no longer rotates To dismount Rotate counterclockwise until the lever no longer rotates To connect the cable to unthreaded terminal use bar type crimp style terminal Not doing so may result in fault...

Page 12: ...oster might discolor and begins to burn because of the heat of the illuminator Caution Duct Opening Duct cover Use the poster clip to suspend a work instruction sheet or process chart from the Factory Line 20 Fold down about 10 mm of the top of the work instruction sheet or process chart and slide it sideways into the poster clip The work instruction sheet can be positioned in the desired directio...

Reviews: