Technical/Programming Manual
FT1020G3 Rev 2.2.1
145
Silence Buzzer with Door Switch:
If the buzzer in the CIE is to be silenced
when the door is opened, this checkbox should be marked.
Redundant TLON Network
: This checkbox is to be marked when two TLON
Networks to be used, i.e. each Control Unit in the system is equipped with two
TLON connection boards (5090). See also chapter "TLON connection board 5090",
page 50.
Flash LED on MCP:
The manual call point (type 3333 / 3339 / 4433 / 4409)
built-in LED will flash to indicate communication with the CIE
Checkbox not marked = This option is disabled, i.e. the LED is switched off until
the call point is operated.
Green polling LED
:
Valid for the detectors 440x in Advanced mode only. The detectors 4400 and 4401
have a green polling LED.
Always off = The green polling LED is not used.
Flash when polled = The green polling LED will be blinking 20ms / 7 sec.
indicating the communication with the CIE.
Note:
When the detector is in test mode the green polling LED will be turned off until the
test mode is turned off
Enhanced disablements:
Disabled alarm point
152
will not activate pre-
warning, fire alarm or fault.
Checkbox not marked = Disabled alarm point
will not activate pre-warning or fire
alarm. Fault can still be activated.
This is a violation to the AS7240.2 standard.
21.1.4.1
Door closing by time
Active
: If all fire doors (trigger condition "Fire Door Closing") required to be closed
at a certain time every day, this checkbox is to be marked and the time (
hh:mm
)
set, e.g. 23:00.
21.1.4.2
Main power loss fault delay time (minutes)
A fault will be activated
mm
minutes after loss of mains (230V
AC
). 30 is default. 0-300
minutes can be selected.
152
The sensor values for a disabled analogue smoke detector will not be saved.