Table 18 Other units current consumption
Other units
Normal state
(quiescent) (mA)
Alarm state
(activated) (mA)
Routing equipment (Fire brigade TX / Fault TX)
See foot note
180
See foot note
External Presentation unit 1728
26
@24 V / 48@12 V
49
@24 V / 88@12 V
Alert Annunciation unit 1736
26
@24 V / 48@12 V
42
@24 V / 79@12 V
Alarm devices (sounders, etc.)
0
Sounder type current
Occupant Warning System (OWS) 60W
181
118
3100
Magnetic door holder
Approximately 80
0
As more
loop devices are added, they are summarised in the “Summary of loop units”
providing information for total quiescent and maximum consumption in the “Properties for
NMAST loop” dialog box. See Figure 57 below for steps to access the information from
EBLWin under their respective loops.
Figure 57 Access to COM loop units current consumption
The current consumption of FT1020G3 from the power supply and the charging current for
the battery with battery temperature can be displayed via menu H5/A4.
An approximate value of individual COM loop is also displayed via menu H5/A5.
180
Quiescent and alarm current must be added correctly for each brigade unit e.g. Romtec, Tyco ASE, etc. Separate power supply
and batteries may be required.
181
OWS with higher wattage e.g. 120W or 250W requires separate power supply and battery backup.