Technical/Programming Manual
FT1020G3 Rev 2.2.1
18
Table 2 Control Panel Limitation
Item
C.I.E.
Network System
General fire alarm via programmable input
100
External fault via programmable input
50
30 x 50
Programmable inputs
512
Programmable outputs (= control expressions)
9
512
Technical warnings
100
30 x 100
Addressable 2 voltage outputs unit 3364
40
External display units
16
30 x 16
Interlocking Combinations
400
4000
10
Presentation numbers / alarm points
11
that can be presented
in the display(s) in case of fire alarm
512
512
Presentation numbers
8
that can be programmed
512
30 x 512 = 15 360
Zones that can be programmed
512
12
999
Faults
300
Disabled zones
512
Disabled alarm points (zone/address) + Disabled COM loops
200
13
Disabled outputs
200
14
Disabled interlocking outputs
200
15
Sensors activating SERVICE signal
200
AAF zones (Max. 5 detectors per AAF zone.)
16
100
30 x 100
Total number of expansion boards 4580, 4581 and
4583
17
6
30 x 6
Number of I/O matrix boards 4582
18
24
30 x 24
Total number of 4582 for zone control and generic applications
6
30 x 6
Number of user definable text message programmed per 1728
and 1736
617
9
Approx. 4000 trigger conditions can be used in these control expressions, more outputs can be used without control expression
(V2.1.1 and higher).
10
Max. 100 user definable texts can be displayed "at the same time".
11
Presentation number is a ZONE only or ZONE
– ADDRESS.
12
Any zone number between 001 and 999 can be used for the 512 zones.
13
Zone/address disabled via time channel not included.
14
Control outputs disabled via menu H2/B3 and Alarm devices disabled via menu H2/B4 are not included.
15
Interlocking outputs disabled via menu H2/B3 are not included.
16
Used in conjunction with the Alarm Acknowledgement Module (AAM).
17
Expansion boards 4580, 4581 and 4583 are physical connected to COM loop 0
18
Reduce no. of 4582 boards by one for every expansion board used (4580, 4581 or 4583).