Each 3364 unit also has one programmable special output, intended for fire door closing
(release magnets) only:
Output VO2
Voltage output, 24V
DC
, max. 1A
85
. Normally high. For more
information see the Addressable 2 voltage outputs unit Technical Description.
24V
DC
is required from an external power supply unit (e.g. 3366AU).
Connections and more information, see drawing F733 & F737.
12.7
The 4477 unit's Output (siren)
Each 4477 unit has one programmable output:
Output
Siren,
with three priority levels and three types of tones.
Connections and more information, see drawing F733.
12.8
The 3379 unit's Output (sounder)
Each 3379 unit has one programmable output:
Output
Sounder,
Three priority levels and three types of tones.
Also "High sound output" can be selected (4.5 dB).
Connections and more information, see drawing F733
12.9
The 4380 unit's Output (beacon)
86
Each 4380 unit (under obsolete loop units) has one programmable output:
Output
Beacon
(Light output 1 Cd. Flash rate 1 Hz.)
Connections and more information, see drawing F733.
Note
: This unit is no longer to be found in Panasonic's product range.
12.10
The 4383 unit's Output (light indicator)
87
Each 4383 unit has one programmable output:
Output
Light indicator
(Flash rate 1 Hz.)
86
The unit is discontinued and will be replaced with a new approved strobe to EN54.23.
87
4383 is discontinued, it is not complying with the new standard EN54.23 however the unit still can be used in the AU or NZ
markets until a compliant unit is released.