Technical/Programming Manual
FT1020G3 Rev 2.2.1
91
Other
43. The control expression is true (output activated) when LED "Fire brigade TX"
is lit, i.e. when any "Fire brigade TX" output is activated (default) or when a
programmable input with trigger condition "Activated Routing Equipment" is
activated
101
.
44. The control expression is true (output activated) when LED "Fault TX activated"
is lit, i.e. when the routing equipment output (Fault TX) is activated
102
.
45. Output activated when one or more faults are generated in the system
103
.
46. Output activated for loss of mains (in the CIE or external power supply 3366AU)
104
.
NOTE:
The output(s) will be activated immediately but the corresponding fault is
normally delayed (set via EBLWin).
47. The control expression is true (Output activated) for 5 seconds whenever a reset
pulse is sent to the specified Zone-Address. The control expression can only be
used in the CIE as the specified Zone-Address
48. Output activated when the specified time channel is activated.
49. Output activated when Alert annunciation alarm is activated (by any alarm point
set to activate this function).
105
For more information, see FT1020G3 Operation
Manual.
50. Output activated when Alert annunciation alarm is activated (by any alarm point
set to activate this function)
and acknowledged. For more information, see
FT1020G3 Operation Manual.
51. Output activated when door open in any Control Unit in the system.
106
52. This trigger condition plus the OR operator has to be used for each detector (zone-
address) controlling a fire door (normally > two detectors). Type of output is
normally "Control, neutral". See also chapter "Fire Door Closing", page 101.
53. Output activated when service signal is activated (by any sensor).
107
54. The control expression is true (output activated) when the Control Unit standard
output "Fire brigade TX" is activated.
Used for example when a standard “Fire
brigade tx” voltage output is required. Used with output type
Routing equipment
(Fire brigade tx)
.
NOTE:
If the Control Unit
has “selective fire alarm presentation”, the standard
output(s) will also be selectively activated.
55. Output activated for door open in the specific Control Unit.
108
56. Output activated when input trigger condition "Extinguishing system fault" is true.
57. Output activated when input trigger condition "Extinguishing system released" is
true.
101
This output will also be activated when the routing equipment test is performed via menu H1. This trigger condition
must not
be used for type of output "Routing equipment (Fire brigade TX)".
102
Indicated by LED
Routing equipment
"Fault TX activated". This output will also be activated when the routing equipment
test is performed via menu H1.
103
Indicated by LED
Fault / Disablements
"General fault" and/or LED
Routing equipment
"Fault TX activated".
104
Indicated by the symbol
in the CIE display.
105
Valid until the AA alarm is reset or becomes a normal fire alarm.
106
Or external FBPs connected to the control unit(s).
107
Indicated by a "Service" symbol
in the display symbol area.
108
Indicated by the "Door open" symbol
in the display symbol area.