108
Operation Manual
FT1020G3 Rev 2.10.4
Automatically (by the S/W itself) S/W watchdog. FFD, WASV SSD, S/W, SSW
13
Automatically due to external disturbance.
FFD, WASV SSD, S/W, SSW 01, 02 alt.
04-12
Note
: During a restart, the fault output (relay) for the Fault TX will be "activated" for few
seconds, the supervised 24 V
DC
outputs S0-S3 will not be supervised and S0-S3
programmed as normally high will be low for few seconds.
21.2.1
Explanation of Restart Codes
•
Code 00 displays after manual power on/off or S/W download.
•
Code 03 will display after a normal restart.
•
Code 13 is always followed by an address, to be noted.
•
Code 25 displays after download of SSD and automatic restart.
•
Code 50 & 53 will display only if the FDCIE has an MMI board.
Note
: Code 00 – 49 = Main board restart. Some data might be lost, see above.
Code 50 – 99 = MMI board restart. No data is lost.
21.3
During Restart
During "restart", no fire alarms will be activated and the following is shown on the display:
And after few seconds (the control panel starts the normal restart procedures else see
Memory fault below):
A fault
will be generated, the buzzer will sound and the following text message will be
shown in the display:
Regarding code
xx
and address
yyyyyy
, see Table 18 above.
This fault is also indicated by LEDs
Routing equipment
"Fault TX activated" and
Fault /
Disablements
"General fault".
After the fault is acknowledged (via menu H6 or EBLWin), the LEDs will be turned OFF, if
no other faults exist in the system.
After any restart, if any units were disabled before restart, an individual disablement for
these units should be done.
FAULT: Restart Control Unit nn, code xx,
address yyyyyy
Booting......
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...