23.1
Zone or Zone Address (H2/B1)
When a whole zone is disabled, all alarm points within the zone are disabled. Alarm points
can be individually disabled
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H2.
H2 Disable or re-enable
"
↵
"
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
- Via
menu B1,
a Zone
or an alarm point (Zone
/ Address) can be
disabled.
- A time for automatic
re-enablement can be
set.
- Disabled zones and
alarm points are shown
in a Re-enable list.
Escape
menu
"
↵
"
Disable
Zone
0
00
Automatic re-enable: No
Use the soft key
"Change type of
disablements" to toggle
between:
Zone
000 and
Zone
000..
address
00.
Change type
of disablement
"Change type of
disablements"
Disable
Zone
0
00 address 00
Automatic re-enable: No
Write the zone number
and address.
To set an automatic re-
enable time press "▼"
and "►". Write the time
(default is current time +
3 hours). Press "
↲
" to
disable, which will be
indicated with "
√
" and a
beep. The zone will be
automatically shown in
the Re-enable list
Change type
of disablement
Write the zone number
and address
(e.g. 003, 01).
"▼"
"►"
"
↲
"
Disable
Zone
0
03 address 01
√
Automatic re-enable: No Yes, at 17:05
-- Re-enable list (1) ---------------------------------------------
Zone 003 address 01 auto. re-enable at 17:05
If the specified zone /
unit is not existing, it will
be indicated with "X"
instead of "
√
" and a
beep.
Use the soft key "
|
" to
toggle between
Disable
and
Re-enable
list
.
Change type
of disablement
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...