137
Operation Manual
FT1020G3 Rev 2.10.4
26.2
Sensitive Fault Detection Mode (H5/A2)
During commissioning, the "Sensitive fault detection mode" can be used to enable the
commissioning personnel to detect the faults faster than normal mode. The time delay for
each fault will then be reduced, i.e. you may find some faults now instead of later.
When the "Sensitive fault detection mode" is turned on, it is indicated by the LED
Routing
equipment
"Fault TX activated", "Fault" output for routing equipment is "activated" and the
search symbol
appears in the symbol area of the display.
Note: Don't forget to turn off this mode after the commissioning.
Action
Text in display
Comments
"
Menu
"
According to chapter
"Access", see page 42.
Scroll to menu H5.
H5 Service
"
↲
"
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in control unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A2.
A2 Sensitive fault detection mode
"
↲
"
Sensitive fault detection mode is not active
Press
↲
to activate
"
↲
"
Sensitive fault detection mode was activated
Press
↲
to deactivate
"
↲
"
Sensitive fault detection mode is not active
Press
↲
to activate
"
ESC
"
A2 Sensitive fault detection mode
Scroll to another menu
or press "ESC".
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...