140
Operation Manual
FT1020G3 Rev 2.10.4
26.5
Display Current Consumption on COM-loop (H5/A5)
The current consumption (an average value) for each COM loop can be displayed.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H5.
H5 Service
"
↲
"
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A5.
A5 Display current consumption on COM-loop
"
↲
"
Display current consumption on COM-loop:
0
control unit: 00 (press
↵
)
Write loop number and
control unit number and
press "
↲
".
"
↲
"
Please wait......
No reply from control unit.....
If the control unit is
existing or doesn't
respond.
Current consumption on COM-loop: 0
control unit 00 is xxxx mA
The current
consumption accuracy is
±5 mA. Information is
automatically updated
every 5 seconds
"
↲
" or "ESC"
A5 Display current consumption on COM-loop
Scroll to another menu
or press "ESC".
Note 1:
No or very small current consumption (< 10 mA) cannot be presented correctly /
precisely since the accuracy is ±5 mA.
Note 2:
If you get “No reply from control unit.....” the control unit don't exist or don't answer.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...