141
Operation Manual
FT1020G3 Rev 2.10.4
26.6
Display Statistics for Communication (H5/A6)
The statistics can be used during commissioning, service, etc.
Number of pollings
is the number of pollings / "questions" sent out by the Control Unit to
all the units connected on the COM loop.
Parity fault
is the received number of parity faults and % (faults in relation to pollings).
Number of bit faults
is the received number of bit faults and % (faults in relation to
pollings).
No answer
is the received number of answer faults / no answers and % (faults in relation
to pollings).
Bit length fault
is the received number of bit length faults and % bit length faults in relation
to the pollings.
The number of Parity faults, number of bit faults, no answer and Bit length faults should be
normally "0" or as close to "0" as possible. If not, there are some communication problems
that have to be investigated. Check the COM loop, connections and the loop units.
All values are set to "0" after restart and/or after re-connection of COM loop (via menu
H8/S1).
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H5.
H5 Service
"
↲
"
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A6
A6 Display statistics for communication
"
↲
"
Display statistics for COM-loop:
0
control unit: 00
Write loop number and
control unit number and
press "
↲
".
"
↲
"
Please wait......
No reply from control unit.....
If the control unit is not
existing or doesn't
respond.
Number of pollings: nnnnnnn
Parity fault: 000000 00.0%
Number of bits fault: 000000 00.0%
No answer: 000000 00.0%
Bit length fault: 000000 00.0%
Note
: The values are
not live updated.
"
↲
" or "ESC"
A6 Display statistics for communication
Scroll to another menu
or press "ESC".
The information is automatically updated every 5 seconds
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...