142
Operation Manual
FT1020G3 Rev 2.10.4
26.7
Activate Address Setting Mode for DU (H5/A7)
This function can be used by commissioning / service technicians to activate the address
setting mode
in the following Display Units connected to the FDCIE:
•
External Presentation units
•
Alert Annunciation units
•
General Control Panel
A specific unit or all units connected to one FDCIE can be activated for address setting.
Note:
The units should be in operation and in quiescent condition, i.e. the units should have
already an address.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H5.
H5 Service
"
↲
"
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A7
A7 Activate address setting mode for DU
"
↲
"
Activate address setting mode for DU:
Control unit:
0
0, display unit: 00 All
Write control unit
number, and the unit's
address or press "►" to
select "All" (i.e. all
display units on the
selected control unit).
"
↲
"
Address setting mode for display unit 00,
control unit 00 activated
The address can now be
edited in the display unit
(DU) respectively.
"
↲
" or "ESC"
A7 Activate address setting mode for DU
Scroll to another menu
or press "ESC".
43
As an alternative, the address setting mode can be activated via jumper "J4" inside the display unit.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...