15
Operation Manual
FT1020G3 Rev 2.10.4
3
Fire Detection Control & Indicating Equipment
(FDCIE)
3.1
FT1020G3 Specifications
Table 2 Control unit specifications
Item
Specifications
Mains Voltage
230V
AC
(195-253), 2 A
System Voltage
24V
DC
@ 6.5A
Current Consumption
Quiescent / alarm current is calculated by EBLWin and is
dependent on other equipment fitted in FT1020G3, type and
number of expansion boards, connected external equipment, etc.
Ambient Temperature (
⁰
C)
Operating 0 to + 40, Storage -40 to +70
Ambient humidity (%RH)
Maximum 90, non-condensing
Cabinet Size (mm)
Small 19” cabinet 13U, 700H x 600W x 250D
Large 19” cabinet 22U, 1050H x 600W x 250D
Battery box 19” cabinet 6U, 350H x 700W x 250D
Enclosure Material
1.5 Zinc annealed steel
Enclosure Colour
Oyster, ripple finish
Approvals
AS7240.2:2018, AS7240.4:2018, AS4428.3:2020 and
NZS4512:2010
Standard Inputs / Outputs
Four COM loops (0-3), each loop can connect up to 253 devices
Four programmable non-supervised / supervised inputs (N/O or
N/C) I
0
-I
3
Four Programmable Supervised Voltage Outputs, 0.5 Amp each
Two Programmable Relay Outputs, contact rating 2 Amp
Two non-programmable relay outputs for ASE (fire & fault)
Six x 24V
DC
outputs for Web server, ASE, Remote Display Units,
external applications 0.5 – 3.15 Amp.
Expansion Boards
Max. 6 of 4580 or 4581 or a combination
of both.
I/O Matrix 4582 board
Max. 24, 6 per COM loop if no Expansion Boards on Loop 0
fitted. Up to 6 modules can be used as zone or g 18 Fan
Control Modules (4 fans per module)
Note
: I/o matrix 4582 is now integrated in the new zone control 1205, fan control 1206 and
damper control 1211 modules, same limitations apply. Refer to Chapter 5, page 28.
1
Refer to G3 block wiring diagrams shown in chapter 34, Figure 24 page 176
2
First input I
0
cannot be used in NZ convention, only 3 programmable inputs are available.
3
Expansion boards are internally connected to COM loop 0, ensure total number of Expansion Boards and
modules with built-in I/O matrix connected to COM loop 0 does not exceed 6.
4
Reduce the number of modules containing 4582 connected to COM loop 0 by one for every Expansion Board
used.
5
If no Expansion Boards fitted, up to 24 fan/damper control modules can be used i.e. 96 individual fan/damper
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...