158
Operation Manual
FT1020G3 Rev 2.10.4
29.6
Activate Address in Alarm Mode (H8/S6)
One alarm point (zone-address),
not a whole zone
, can be set in alarm. It will be presented
in this Control Unit as a fire alarm, the built-in LED in the alarm point e.g. a detector, will be
turned on.
Note
: All outputs, standard and programmable, which would have been activated by a real
fire alarm from the same alarm point, will now be activated.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H8.
H8 Maintenance
"
↲
"
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
Scroll to menu S6.
S6 Activate address in alarm mode
"
↲
"
Select zone:
0
00 address: 00
(press
↵
)
Write the zone number
and address (e.g. 123-
45).
"
↲
"
Select zone: 123 address:
4
5
(press
↵
)
"
↲
"
First alarm: 123-45
1
zone in alarm
Latest alarm: 123-45
-------------------------------------------------------------------------
-----------------
Select zone:
1
23 address: 45
(press
↵
)
Press "ESC" to exit this
menu.
The fire alarm has to be
reset as a normal fire
alarm (press "Reset").
"Reset"
"ESC"
S6 Activate address in alarm mode
Scroll to another menu
or press "ESC".
First alarm: 123-45
Alarm number 1(of 1)
This manually activated
fire alarm will be
presented as Test mode
alarm” in all control units
and indicated by the
LEDs "Fire" (L1) and
"Fire brigade tx" (L4).
This manually activated
fire alarm must be reset
by the push button
"Reset" (P3)
Test mode
Zone Address
123-45
SMOKE
Alarm text for 123-45
Menu
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...