19
Operation Manual
FT1020G3 Rev 2.10.4
Note
: “Alarm Routing Activated” LED will be replaced by “ASE Activated” in the revised
front to fulfil AS4428.3:2020
The Fire Brigade Panel (section framed by red boarder) is integrated in the main FT1020G3
front display. FBP is normally used by fire services personnel to investigate which alarm
point / zone(s) have activated a fire alarm and take the required operational control of the
system. Fire brigade personnel can control active alarms via the buttons and keys P1-P4
and P9 within the FBP. P5 – P8 buttons are used to navigate the menu. In the graphical
display, the information displayed in the upper part is dependent on how many alarm points
/ zones have generated fire alarm. In the middle part, the fire alarms will be shown, i.e. one
alarm point or one zone together with a user definable alarm text (if programmed) plus
some other information.
The Control Panel CP is used to "communicate" with the system, i.e. for commissioning,
monthly tests, maintenance, etc. Access code for different access levels is required. To get
access to the system (a menu tree with main and sub menus) and for operational control
of the system, up to ten User names can be used for three different User level types. A
Password (six digits) for each user name is required to logon to the panel and Webserver.
3.4.1
LED Indicators and Push Buttons
LED’s and push buttons are contained on the front panel display and are described
, for the LEDs and push buttons.
3.4.1.1 Fire Brigade Panel Display and Control
Table 4 LED indicators and push buttons on Fire Brigade Panel (FBP)
No Label
Colour Indicating / Action
L1
Fire
5xRed
Fire alarms. See chapter "Alarm types", page 57.
L2
Fire Protection
Activated
Red
Output(s) for extinguishing (suppression) equipment
activated. (Or a programmable input type "Extinguishing" is
activated.)
L3
Smoke Control
Activated
Yellow
Output(s) for smoke control ventilation equipment (AS1668)
activated (fan / damper). Or a programmable input type
"Ventilation" is activated.
L4 ASE (Alarm Routing)
Activated
Red
Output "Fire alarm" for Fire Brigade TX and/or
corresponding programmable output(s) of type
"FireBrigadeTx") is/are activated (or a programmable input
type "Activated routing equipment" is activated.) or testing of
routing equipment in progress.
L5
Power
Green
Steady: FDCIE is powered via the primary power supply
and/or the battery.
Flashing: FDCIE start up.
L6
Several Alarms
2xRed
Multiple units / zones have activated fire alarm. Use push
button "Several Alarms" (P9) to scroll amongst the alarm
points (zone-address) or soft key "Next zone" (P6) to scroll
amongst the zones.
P1 Silence Buzzer
White
Used to silence the buzzer in the FDCIE when it is sounding
P2 Silence Alarm
Red
Used to silence alarm devices e.g. OWS / sounders in the
building when they sound. Silenced alarm devices is
indicated to the right in the display's soft key area (a symbol
page 21.
P3 Reset
Green
Used to reset fire alarms, only after all fire alarms have been
silenced, see "Fire alarm reset", page 68.
Note:
P3 has to be pressed for > 0.5 sec.
P4 Disable
Yellow
Used to disable active alarm(s), all outputs of the device or
zone in alarm will be disabled and reset after fire alarm
devices have been silenced.
P5
to
P8
Soft keys
Grey
Operation/function is shown above each key in the display
i.e. soft key area. The function of a soft key may vary
depending on the FDCIE condition. If no text is shown above
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...