33
Operation Manual
FT1020G3 Rev 2.10.4
5.4
Addressable COM Loop Display Modules
The ancillary 3U rack is designed to be fitted with any combination of display modules as
shown in Figure 12 below.
Figure 12 3U Ancillary Modules Face Plate
Any combination of modules in Figure 13 to Figure 16 will fit onto the 3U Ancillary Modules
Face Plate shown in Figure 12 These provide maximum flexibility for controlling and
indicating of programmable inputs and outputs when used with FT1020G3 Addressable
FDCIE loaded with software ≥
V2.4.x.
Note
: Modules with separate I/O matrix 4582 can be used with software prior to V2.4 whilst
modules with built-
in I/O matrix circuit e.g. 1205/1206/1211 must be used with software ≥
V2.4
.x . Other modules 1204, 1207, 1208, 1209 and 1210 must use ≥ V2.4.x.
Total capacity of a single 3U 19” rack is 420mm, first 20mm is always allocated for power
monitor module. The other 400mm can be used to mount multiple different modules. Some
modules require 1 space (50mm), others require 2 spaces (100mm). Blank modules are
also available to fill up the gaps for any unused modules in the rack.
All modules follow a similar pattern and are designed to be mounted on the 19” metal 3U
plate and secured by suitable hardware. A rectangular washer (PCB) is used to help retain
the adjacent module. The modules are interconnected by a single ribbon cable part number
CA380. A blank module 10HP (50mm) is used to cover an unused module space. Also
available is a Blank Module 4HP (20mm) used to blank out the space reserved for the 1204
Power Monitor Module when 3U Ancillary Modules are used.
The new display modules are versatile and interchangeable modules allowing for quick and
easy installation and configuration as shown in Figure 12. The modules are mounted from
the rear of the ancillary rack using supplied prolong washer (or small PCB) and fasteners.
The functions and features of the new display modules are shown in Table 12 below.
Table 12 Module specifications
Module
No.
Description
Inputs to
FDCIE
Indicators
No. of
Add.
Module
space
1204
Power Monitor Module
24V and 5V power
fail
Poll, 24V OK, 5V OK
1
20 mm
1205
15 Zone Control Module
Disable zone
Disable, Fault and Alarm
LED
1
100 mm
1206
4 Fan Control Module
On, Auto, OFF
Fire Mode, Run, Stop,
Fault, Phase
Fault, On, Auto, Off
1
100 mm
1207
8 Key / 8 LED Control and
Display Module
8 programmable
Switches (input)
8 Programmable LED’s
(output)
2
50 mm
1208
4 Key / 8 LED Control
and Display Module
4 programmable
Switches (input)
8 Programmable LED’s
(output)
2
50 mm
1209
8 LED Display Module
N/A
8 Programmable LED’s
(output)
1
50 mm
1210
6 LED Pump Status
Display Module
N/A
6 x Programmable LED’s
(output)
1
50 mm
1211
4 Damper Control
Module
Fire, Auto,
Non- Fire
Fire Mode, Fire, Non-Fire,
Fault, Power Fault, Fire,
Auto, Non-Fire
1
100 mm
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...