Table 14 Damper indicators and controls
LED indicator & buttons
Indicating
FIRE MODE General fire mode - Red Illuminates to indicate general fire.
FIRE
Damper open - Red
Illuminates to damper is opened.
NON- FIRE Damper close - Green
Illuminates normal status i.e. damper closed.
Fault
Fan fault - Yellow
Illuminates when the signal to change the damper status
is restored, either via manual override switch or by the
FDCIE in Auto mode but the feedback signal confirming
the change of damper state has not been received by
4461 input connected the damper field control (if used).
Or
There is an open circuit in the 4461 supervised input
where the feedback from the field damper control is
connected.
Or
The damper device suppling damper condition is faulty
POWER
FLT
Power fault - Yellow
Illuminates in case of no power controlling the damper
FIRE
LED – Red
Indicates manual control when the “On” button is pressed
Button
Manual override control to open the damper manually
irrespective of any alarm condition in the FDCIE.
AUTO
LED – Green
Indicates “Auto” position of the button, normal operation
Button
Pressed to put the damper in “Auto” mode i.e. the
damper
may open or close automatically depending on the
alarm condition in the FDCIE
NON FIRE
LED - Yellow
Indicates “Off” position of the button, damper close
manually
Button
Manual override control to close the damper if it was
opened
irrespective of any alarm condition in FDCIE.
5.5
Generic FT1020G3 Display and Control Modules
Each 19” rack mount display / control module comprises 3 parts: PCB, plastic spacer and
decal label. The PCB for all display modules is only one PCB but fitted with switches and
LEDs to suit different applications. All switches and LEDs are fully programmable in
EBLWin as an input (switch) or as an output (LED).
Each display module can be manually addressed with the address setting tool set to
Advanced Mode.
All Disp
lay Panel modules must be configured with software ≥ V2.4.x. to
be recognised by the FDCIE.
The generic and display modules are mounted on the ancillary 19” metal rack, up to 8
modules can be connected on an ancillary rack. Each module required to be connected to
the monitor card 1204 via a ribbon cable to communicate with the loop and to provide 24V
/ 5V supply. The ribbon cable is equipped with 10 way socket to plug in the IDC header in
each module.
All LEDs in every module can be configured via DIP switch on each module to provide 3
colours; red, green and amber. Even within the same module, different colour indicators
can be configured.
Notes:
1205
,
1206
&
1211
: Only addresses 0-5 can be assigned. I/O matrix type selection is not
required, permanently selected for each type.
1207
&
1208
: Require 2 consecutive COM loop addresses per module and will
automatically take on the next address.
The four 50mm different display and control modules are shown in Figure 16 below. The
functionality and requirements are described in section 5.5.1 to 5.5.4 below.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...